Specifications

Product Type UPS
Sub Brand SteadySine™
Region EMEA
UPS Topology Double Conversion
Phase 1
Nominal Input Voltage (V) 220/230/240
Input Frequency Range (Hz) 40 - 70 (auto sensing)
Input Plug Schuko CEE 7/EU1-16P and BS1363A
Input Cord Length (ft.) 10
Input Cord Length (m) 3
Output Capacity (kVA) 2
Output Capacity (kW) 2
Output Power Factor 1
Frequency Compatibility (Hz) 50
Output AC Waveform (AC Mode) Pure Sine Wave
Output AC Waveform (Battery Mode) Sine Wave
Nominal Output Voltage (V) 220/230/240
Output Receptacles (8)C13
Outlet Bank Switching Yes
Battery Type Lithium-Ion
Battery Voltage (V dc) 72
Battery Charge Time (h) 1-3 to 90%
Internal Battery Replacement Method Hot Swap
Internal Replacement Battery Cartridge ULC272
Front Panel Display LCD
Alarm Silence Operation Yes
Audible Alarm Yes
Surge Protection Rating ANSI C62.41 Category A
Mount Orientation Horizontal/Vertical
Number of Rack Units 4
Cooling Method Fan
Optional Mounting Accessories U2PTRMT
Overall Depth (In.) 19.6
Overall Depth (mm) 500
Overall Height (In.) 3.4
Overall Height (mm) 86.5
Overall Width (In.) 17.3
Overall Width (mm) 440
Minimum Operating Temperature (°C) 0
Minimum Operating Temperature (°F) 32
Maximum Operating Temperature (°C) 40
Maximum Operating Temperature (°F) 104
Power Module Minimum Storage Temperature (°C) -25
Power Module Minimum Storage Temperature (°F) -13
Power Module Maximum Storage Temperature (°C) 55
Power Module Maximum Storage Temperature (°F) 131
Minimum Relative Humidity (%) 0
Maximum Relative Humidity (%) 95
Online Thermal Dissipation (Full Load) (BTU/h) 142
Online Mode Efficiency Rating (100% Load) (%) 92
Operating Elevation (ft.) 9843
Operating Elevation (m) 3000
Audible Noise (dBA) 55
Network Card Yes
Software Compatibility DCIM Ready
Network Compatibility SNMPv3
Communications Interface RS-232, Ethernet
Emergency Power Off (EPO)/Remote On-Off (ROO) Yes
Transfer Time (ms) 0
Cold Start Support Yes
Grounding Method Lug
Application Data Center, Edge, Enterprise MTDC
Compliance Certifications CB: IEC 62040-1:2017, CE-LVD: EN 62040-1:2008+A1: 2013, IEC 62133 (cell), IEC 62619 (pack),IEC 62040-2-2016, EN 62040-2-2018, BS62040-2-2018, ISTA Procedure 2A, UN 38.3
Product Warranty Period (Worldwide) 5 Years

Runtime Graph

The interactive graph below shows actual measured runtime data for this UPS. Hover over the graph and refer to the chart on the right to see the expected runtime for your specific load and configuration, and for reference. Note that actual runtimes may vary based on several factors, such as battery age, charge level, environmental conditions, and connected load. Actual runtime may vary from +/- 15% around these typical values. *EBP = External Battery Pack

Load(Watts): -
Show
Type
Runtime
0 EBP
-
Configuration500 VA Load1000 VA Load1500 VA Load2000 VA Load
0 EBP36 minutes18 minutes12 minutes9 minutes

Packaging Detail

UPC 61305682537
Std. Pkg. Qty. 1
Std. Pkg. Volume (cf) 4.7225
Std. Ctn. Qty. 0
Std. Ctn. Volume (cf) 0.0000
Compare