Specifications

Product Type UPS
Sub Brand SteadySine™
Region EMEA
UPS Topology Double Conversion
Phase 1
Nominal Input Voltage (V) 220/230/240
Input Frequency Range (Hz) 40 - 70 (auto sensing)
Input Plug Schuko CEE 7/EU1-16P and BS1363A
Input Cord Length (ft.) 10
Input Cord Length (m) 3
Output Capacity (kVA) 3
Output Capacity (kW) 3
Output Power Factor 1
Frequency Compatibility (Hz) 50
Output AC Waveform (AC Mode) Pure Sine Wave
Output AC Waveform (Battery Mode) Sine Wave
Nominal Output Voltage (V) 220/230/240
Output Receptacles (8)C13, (1)C19
Outlet Bank Switching Yes
Battery Type VRLA
External Battery Pack Compatibility UVP072
Battery Voltage (V dc) 72
Battery Charge Time (h) 4-6
Internal Battery Replacement Method Hot Swap
Internal Replacement Battery Cartridge UVD072
Front Panel Display LCD
Alarm Silence Operation Yes
Audible Alarm Yes
Surge Protection Rating ANSI C62.41 Category A, Level 2
Mount Orientation Horizontal/Vertical
Number of Rack Units 2
Cooling Method Fan
Optional Mounting Accessories U2PTRMT
Overall Depth (In.) 23.6
Overall Depth (mm) 600
Overall Height (In.) 3.4
Overall Height (mm) 86.5
Overall Width (In.) 17.3
Overall Width (mm) 440
Minimum Operating Temperature (°C) 0
Minimum Operating Temperature (°F) 32
Maximum Operating Temperature (°C) 40
Maximum Operating Temperature (°F) 104
Power Module Minimum Storage Temperature (°C) -25
Power Module Minimum Storage Temperature (°F) -13
Power Module Maximum Storage Temperature (°C) 55
Power Module Maximum Storage Temperature (°F) 131
Minimum Relative Humidity (%) 0
Maximum Relative Humidity (%) 95
Online Thermal Dissipation (Full Load) (BTU/h) 890
Online Mode Efficiency Rating (100% Load) (%) 92
Operating Elevation (ft.) 9843
Operating Elevation (m) 3000
Audible Noise (dBA) 55
Network Card Yes
Software Compatibility DCIM Ready
Network Compatibility SNMPv3
Communications Interface RS-232, Ethernet
Emergency Power Off (EPO)/Remote On-Off (ROO) Yes
Transfer Time (ms) 0
Cold Start Support Yes
Grounding Method Lug
Application Data Center, Edge, Enterprise MTDC
Compliance Certifications CB: IEC62040-1:2013, CE-LVD: EN62040-1:2008+A1:2013, RCM UKCA: BS62040-1-2013, IEC 62040-2-2016, EN 62040-2-2018, BS62040-2-2018
Product Warranty Period (Worldwide) UPS Unit: 3 Years, Battery: 2 Years

Runtime Graph

The interactive graph below shows actual measured runtime data for this UPS. Hover over the graph and refer to the chart on the right to see the expected runtime for your specific load and configuration, and for reference. Note that actual runtimes may vary based on several factors, such as battery age, charge level, environmental conditions, and connected load. Actual runtime may vary from +/- 15% around these typical values. *EBP = External Battery Pack

Load(Watts): -
Show
Type
Runtime
0 EBP
-
1 EBP
-
2 EBP
-
3 EBP
-
4 EBP
-
Configuration750 VA Load1500 VA Load2250 VA Load3000 VA Load
0 EBP35 minutes17 minutes11 minutes8 minutes
1 EBP1 hour 47 minutes53 minutes35 minutes26 minutes
2 EBP2 hours 58 minutes1 hour 29 minutes59 minutes44 minutes
3 EBP4 hours 10 minutes2 hours 5 minutes1 hour 23 minutes1 hour 2 minutes
4 EBP5 hours 21 minutes2 hours 40 minutes1 hour 47 minutes1 hour 20 minutes

Packaging Detail

UPC 61305682535
Std. Pkg. Qty. 1
Std. Pkg. Volume (cf) 4.7225
Std. Ctn. Qty. 0
Std. Ctn. Volume (cf) 0.0000